Applies to Models: TID-600R
Summary:
Configuration and connection of door locks to the intercom
1. Select the lock type between N.O (Normally Open/ Fail Secure) and N.C. (Normally Closed / Fail Safe) for the Alarm output 2, and set the duration under the Alarm output setting.
2. If 12VDC power is directly connected to the intercom (recommended to use at least 2A power to provide 550mA out of the intercom.
Follow the wiring as below for N.O. lock type.
2. If 12VDC power is directly connected to the intercom (recommended to use at least 2A power to provide 550mA out of the intercom.
Follow the wiring as below for N.C. lock type.
3. In case you are dealing with N.O. lock that requires more than 550mA, connect a power supply with the higher Amp to the intercom as below
4. In case you are dealing with N.C. lock that requires more than 550mA, connect a power supply with the higher Amp to the intercom as below